4.1 Please follow the transportation warning marks on the package for layer limitation. Do not roll the whole packages when loading or unloading.
4.2 Please keep the compressor always vertically and never upset it during transportation while avoiding any vibration and shock.
4.3 Tumbled compressor cannot be guarantee for norm operation.
4.4 Storage expiry is 6 months from the date of production. If it expired, please check the nitrogen pressure inside compressor and recharge it when it is necessary.
4.5 After pulling off rubber plugs from the compressor tubes, please connect the compressor to the refrigeration system within 5minutes. It is advisable to take off the first plug from discharge tube.
4.6 High voltage test or start test is not permitted under vacuum condition.
4.7 Avoid liquid refrigerant flow into the compressor .
4.8 The earth connection should be fixed firmly.
4.9 The compressor must be mounted horizontally without tilting an angle more than 5.
4.10 The compressor must not be restarted unless at an interval of more than 5 minutes.
4.11 Antifreeze and other unspecified oil is not allowed to use in compressor.